Integrated type 3 overvoltage protection (L-N, L/N-PE), status retrievable via network
High-inrush relay: max. 4 sec: 30 A /max. 20 ms: 80 A
Measurement of key electrical parameters: current (A), voltage (V), phase angle, power factor, frequency (Hz), active power (W), apparent power (VA) and reactive power (VAr)
Measurement of residual current type A (mA)
Encrypted communication through SSL (TLS 1.1, 1.2, 1.3) and SSH
19-inches, 1 HU
LxWxH: 43.9 x 17.8 x 4.4 cm (without mounting brackets)
Weight: approx. 2.9 kg
Operating temperature: 0-50 °C
Storage temperature: -20 – 70 °C
Relative humidity: 0 – 95 % (non condensing)
Electrical Connections
1 power supply IEC C20 (max. 16 A, 230 V) for 8035-1/-2/-3
1 power supply IEC NEMA 5-15 (max. 15 A, 120 V) for 8035-6
8 power ports IEC C13 (max. 10 A) for 8035-1
8 power ports IEC C13 Lock (max. 10 A) for 8035-2
8 power ports Safety socket type F (max. 16 A) for 8035-3
8 power ports NEMA 5-15 (max. 12 A) for 8035-6
1 Ethernet connector RJ45 (10/100 Mbit/s)
1 serial interface RS232 (Sub-D, 9-pin)
2 connectors (RJ45) for plug-&-play sensors
Switching function
Each power port can be switched via HTTP(S), SNMP, ModbusTCP or command line interface via Telnet, SSH, MQTT and serial interface
Programmable on/off sequences for remote reboots (Remote Reboot)
Power ports can be switched when preset sensor thresholds are exceeded
Self-healing function thanks to 8-channel watchdog: Each power port can be assigned its own Watchdog (ICMP/TCP), which initiates an automatic restart if necessary
Switching state and switch-on delay up to 9999 seconds (166 minutes) individually adjustable for each output port after power failure
Current peaks due to increased inrush currents are automatically prevented by sequential switch-on with a latency of 1 second
Metering function
Power consumption metering (kwH) per power outlet with 2 energy counters: one counter counts consistently, the other counter is resettable
Metering of current (A), voltage (V), phase angle, power factor, frequency (Hz), active power (W), apparent power (VA) and reactive power (VAr) per power outlet
2 connectors for combined plug-and-play sensors (temperature, humidity and air pressure) to prevent often occurring physical hazards like overheating and increased humidity or air pressure
Security
Integrated type 3 overvoltage protection prevents damage to the device and connected loads
Long-life High-Inrush Relays prevent welding of relay contacts during inrush current peaks
Generation of status messages and alarms (e-mail, syslog, SNMP traps MQTT, SSH, Telnet)
Encrypted e-mails (SSL, STARTTLS)
Access protection by IP access control
Encrypted communication through SSL (TLS 1.1, 1.2, 1.3) and SSH
Password protected access
Beeper for audible alarm when sensor limits are exceeded/deceeded
IEC-Lock power ports prevent accidental unplugging of power cables (for EPC 8035-2)
Operation
Easy-to-read LED display for displaying total current, IP address and sensor values
Firmware update via Ethernet during operation (no restart required)
Simple and flexible configuration via web browser, Windows or Linux program
Dynamic assignment of an IP address via DHCP or manual assignment of static IP address
Rapid commissioning thanks to free and reliable drivers from our technology partners