Encrypted communication through SSL (TLS 1.1, 1.2, 1.3) and SSH
Housing form: for mounting rail with top hat profile
LxHxD: 143 x 65 x 90 mm
Weight: approx. 400 g
Operating temperature: 0-45 °C
Storage temperature: -20 – 70 °C
Relative humidity: 0 – 95 % (non condensing)
Electrical Connections
1 Mains connection with 230 V AC or 30 V DC (terminal clamps)
8 switching outputs (terminal clamps)
8 passive signal inputs (terminal clamps)
1 Ethernet connector RJ45 (10/100 Mbit/s)
1 connector (RJ45) for plug-&-play sensors
Switching function
8 switchable, potential-free relay outputs with 16 A switching capacity
Each power port can be switched via HTTP(S), SNMP, ModbusTCP or command line interface via Telnet, SSH, MQTT and serial interface
Programmable on/off sequences for remote reboots (Remote Reboot)
Power ports can be switched when preset sensor thresholds are exceeded
Self-healing function thanks to 8-channel watchdog: Each power port can be assigned its own Watchdog (ICMP/TCP), which initiates an automatic restart if necessary
Switching state and switch-on delay up to 9999 seconds (166 minutes) individually adjustable for each output port after power failure
Current peaks due to increased inrush currents are automatically prevented by sequential switch-on with a latency of 1 second
Metering function
1 connection for combined plug-&-play sensors (temperature, humidity and air pressure) to prevent frequently occurring physical hazards such as overheating and increased humidity or air pressure
Security
Generation of status messages and alarms (e-mail, syslog, SNMP traps MQTT, SSH, Telnet)
Encrypted e-mails (SSL, STARTTLS)
Access protection by IP access control
Encrypted communication through SSL (TLS 1.1, 1.2, 1.3) and SSH
Password protected access
Beeper for audible alarm when sensor limits are exceeded/deceeded
Operation
Easy-to-read LED display for displaying total current, IP address and sensor values
Firmware update via Ethernet during operation (no restart required)
Simple and flexible configuration via web browser, Windows or Linux program
Dynamic assignment of an IP address via DHCP or manual assignment of static IP address
Rapid commissioning thanks to free and reliable drivers from our technology partners
เว็บไซต์นี้ใช้คุกกี้เพื่อให้การใช้งานราบรื่นและพัฒนาประสบการณ์ของคุณ การใช้งานต่อถือว่ายอมรับ
นโยบายความเป็นส่วนตัวWe use cookies to improve your experience. By continuing, you accept our Privacy Policy.